C36 Combi
User, Installation and Servicing
Instructions
FAN POWERED HIGH EFFICIENCY
MODULATING DOMESTIC CONDENSING
GAS COMBINATION BOILER
CE/PI No. 86-CM-44
C36 Combi - GC No. 47-930-01
C36P Combi
GC No. 47
-
930
-
02
These instructions must be left either with the
user or next to the site gas meter.
Keston Heating
PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN
Tel. +44 (0) 1482 443005 Fax. +44 (0) 1482 467133
email : [email protected] web :
www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2
SEDBUK A RATED
W D 3 8 8
i s s u e 5 - 2 0 1 1
Vista de página 0
1 2 3 4 5 6 ... 56 57

Resumo do Conteúdo

Página 1 - C36 Combi

C36 CombiUser, Installation and Servicing Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER CE/PI No. 86

Página 2 - CONTENTS

system and burns witha blue flame just off thesurface of the burner.As the hot products ofcombustion passdownwards, they arecooled by e

Página 3 - Page : ii

around 5oC to 10oC above the temperature of the return water. The flue pipe should beterminated outside the building from where they cannot re-ent

Página 4 - 0. HANDLING INSTRUCTIONS

For Timber Framed Buildings, British Gas Publications DM2. Also British GasPublications 'Guidance Notes For The Installation Of Domest

Página 5 - Page : iv

Description Part NumberPre-Installation Jig Plate C.10C.0.11.00.0Flue Terminal Wall Sealing Collar (50mm) C.08.0.00.07.0Air Terminal Wall Sealing Coll

Página 6 - 1. USER INSTRUCTIONS

Seasonal Efficiency (SEDBUK) =90.7 (C36 Combi) & 92.8 (C36P Combi)This value is used in the UK Government's Standard Assessment Pro

Página 7

3. BOILER LOCATION3.1 DIMENSIONS AND MINIMUMCLEARANCESThe boiler must be installed in minimumclearances shown to allow subsequentservicing,

Página 8

applicable in Scotland, with respect to the installation of the boiler in a room or internalspace containing a bath or shower.Where a room-s

Página 9 - 2. GENERAL INSTRUCTION

The method of connection to the mains electricity supply must facilitate completeelectrical isolation of the boiler, preferably by the use of a fused,

Página 10 - Schematic

Gas pressures above or below these levels will lead to problems associated with the gasvalve's internal pressure regulator.Supply pipes to the b

Página 11

k. The boiler is supplied with an integral expansion vessel of 8l capacity. This issuitable for systems of up to 125 Litres syste

Página 12

CONTENTSNB : These instructions are an integral part of the appliance. This document must be handed over tothe user on completion of the installation

Página 13 - (Factory Preset)

driven out of the solution and willcollect in high spots in thesystem. These air bubbles caninterfere with pumping andheat transfer and mus

Página 14

3.8 FLUE SYSTEMNB: When installing a replacement boiler a new flue system must be used. Donot re-use the existing boiler flue installation.3.8.

Página 15 - 3. BOILER LOCATION

There must be no troughs in any of thepipework, whether it be air inlet or flue outlet.Due the low temperature of the flue gases furthercon

Página 16

It is advisable for horizontal flue terminals to place a 45o elbow at the end of theflue to direct the condensate plume up and away from the

Página 17

A minimum slope downwards towards the drain of 1 in 20 is essential. Freezing of thetermination and pipework must be prevented. A

Página 18

4. INSTALLATION OF THE BOILERRead Chapter 3 - Boiler Location and decide upon the position of the boiler.Installation of the boiler is straightforward

Página 19 - Flex Hose

4.3 ASSEMBLY PRACTICERemove all plastic debris and burrs when installing air intake piping. Plastic filings causedby cutting muPVC pipe must not be al

Página 20 - F l o w R a t e ( l p m )

iii) replace the nut from the frame bottomConnect the condensate drainage system to the boiler. It is advisable to use a detachablefitting at connecti

Página 21 - (COMBI P)

4. Securely tighten the terminal screws and route the cable(s) through there-openable cable clips. Ensure all cables are secured and that th

Página 22 - +

5. COMMISSIONING OF THE BOILERImportant: This condensing combination boiler contains components which could be damaged or blocked by grease, dirt,

Página 23

5.7 Combustion Testing5.8 Checking The Gas Pressure5.9 Timing The Gas Meter5.10 Handing Over To The User6 FAULT FINDING6.1 Electrical Control Sequence

Página 24

flow temperature of the boiler. Also press the “Summer” button until the greenlight above this button is extinguished. Once a heating dema

Página 25 - 4. INSTALLATION OF THE BOILER

used during manufacture curing withinthe combustion chamber. On boilerswhich have been fired for more than onehour since installation, the

Página 26

5.9 TIMING THE GAS METERSet the boiler DHW temperature to 65C and open two hot taps in the property fully. Withno other appliances using gas, time the

Página 27

6. FAULT FINDING6.1 ELECTRICAL CONTROL SEQUENCE6.1.1 HEATING DEMANDWhen the external control(s) are calling for heat, power will be fed to the boiler

Página 28

QUICK REFERENCE6.2 NORMAL OPERATIONThe C36 Combi and C36P Combiboilers feature a user displaywhich shows actual flowtemperature at all times wh

Página 29

ERROR CODESAs E41E99Flue sensor open circuit - check connections to flue sensor are in placeE46Flue sensor short circuit - check connections to flue s

Página 30

6.4 FUNCTIONAL FLOW WIRING DIAGRAMWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instru

Página 31

6.5 ELECTRICAL WIRING DIAGRAMWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instructions

Página 32

6.6 ILLUSTRATED WIRING DIAGRAMWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instruction

Página 33 - 6. FAULT FINDING

6.7 Exploded Assembly Diagrams6.7.1 Boiler Controls Assembly WD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallat

Página 34 - 6.3 FAULT MODES

0. HANDLING INSTRUCTIONS0.1 LIST OF CONTENTSThe Keston C36 Combi and C36P Combi are supplied almost totally pre-assembled. The unitsuse standard 50 mm

Página 35

6.7.2 Waterway, Condensate & Flue AssemblyWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servi

Página 36

WD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instructions Page : 3657-25656395657

Página 37 - 6.5 ELECTRICAL WIRING DIAGRAM

6.7.3 Air - Gas AssemblyWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instructions Page

Página 38

6.7.4 Casing AssemblyWD388/0/2004 Chapter 6 : Fault Finding The Keston C36 & C36P Combi BoilersInstallation & Servicing Instructions Page :

Página 39

6.7.5 Exploded Diagrams Parts Reference ListBoiler Controls Assembly (Fig. 6.7.1)GC Number Code Description135 Main Control Box (C.10C.4.01.00.0 B)13

Página 40

7. ROUTINE (ANNUAL) SERVICINGTo ensure the continued safe and efficient operation of the boiler it is necessary to carry outroutine s

Página 41

d. If necessary, from visual inspection, clean the heat exchanger using a suitablestiff plastic bristle brush, vacuum out any large particles and flus

Página 42 - 6.7.3 Air - Gas Assembly

8. REPLACEMENT OF PARTSCONTENTS8.0 GENERAL8.1 PRECAUTIONS8.2 ACCESS8.3 REPLACEMENT PROCEDURE8.4 ELECTRICAL COMPONENTS8.4.1 CONTROL PANEL8.4.2 BOILER F

Página 43 - 6.7.4 Casing Assembly

8.4.2 Boiler Flow and Return Thermistors (Fig. 6.7.2 - 2/3 item 67)i) Isolate the appliance (Section 8.1)ii) Gain access (Section 8.2)iii) Remove the

Página 44

NB: When reassembling inspect any gaskets for damage and replace ifnecessary.8.4.8 Gas Control Valve /Venturi Assembly (Fig. 6.7.3 item 215)i) Isolate

Página 45

side. At this stage it is assumed that the wall bracket is correctly positioned and secured onthe wall face.a) Have the wall bracket nut and washer to

Página 46

iii) Remove the combustion blower (Section 8.4.7)iv) Remove the 4 nuts fixing the burner to the top of the heat exchanger.v) Withdraw the burner from

Página 47 - 8. REPLACEMENT OF PARTS

ii) Gain Access (section 8.2)iii) Shut off the water supply (CWS) to the DHW heat exchanger.iv) Isolate the waterways to the pump using the system iso

Página 48

9. SHORT SPARE PARTS LISTItem GC No Part Denomination Item GC No PartDenomination46 Burner 161 Burner Gasket49 Ignitor Gasket 48 Ignitor/Sensor Probe

Página 49

215 C36 Combi Gas Valve - Mixer Assem. 119 FanC36P Combi Gas Valve - Mixer Assem.135 Control Box 138 Fascia Panel56 Pump Block 57 DHW Heat Exchanger58

Página 50

SHORT SPARE PARTS LIST FOR THE KESTONCONDENSING BOILER RANGEItem GC No Part Denomination46 Burner161 Burner Gasket48 Ignitor49 Ignitor Gasket108 DHW T

Página 51

WD388/0/2004 Chapter 10 : Benchmark Checklist Final The Keston C36 Combi & C36P COMBI Boilers Installation & Servicing Instructions

Página 52 - 9. SHORT SPARE PARTS LIST

WD388/0/2004 Chapter 10 : Benchmark Checklist Final The Keston C36 Combi & C36P COMBI Boilers Installation & Servicing Instructions

Página 53

bRead Installation Manual CarefullybEnsure that ALL dust particles, filings , plastic chips etc. areremoved from the inlet pipe.bIf the i

Página 54 - CONDENSING BOILER RANGE

1. USER INSTRUCTIONS1.1 INTRODUCTIONThank you for choosing this Keston C36 Combi for your household heating and hot waterneeds. The bo

Página 55 - BENCHMARK No

Normal OperationDuring normal operation the digital display will dhow the current boiler temperature and willshow a “.” In the lower right

Página 56 - SERVICE INTERVAL RECORD

your installer at the end of the installation and commissioning process. The details of theChecklist will be required in the event

Página 57 - C36 and C36P Combi

2. GENERAL INSTRUCTION2.1 DESCRIPTIONThe KESTON C36 Combi and C36P Combi combination boilers utilise the latest incondensing technology to