Total Output
Required Kw
Side By Side Option –
Number Of Boilers/Output
Required
Side by Side
Footprint Size
W x D (mm)
Header Kit
Product No.
Side By Side
90 2 x 45 1500x560 355014
100 1 x 45 - 1 x 55 1500x560 355014
110 2 x 55 1500x560 355014
135 3 x 45 2055x560 355015
145 1 x 55 - 2 x 45 2055x560 355015
155 2 x 55 - 1 x 45 2055x560 355015
165 3 x 55 2055x560 355015
180 4 x 45 2600x560 355016
190 1 x 55 - 3 x 45 2600x560 355016
200 2 x 55 - 2 x 45 2600x560 355016
210 3 x 55 - 1 x 45 2600x560 355016
220 4 x 55 2600x560 355016
225 5 x 45 3150x560 355017
235 1 x 55 - 4 x 45 3150x560 355017
245 2 x 55 - 3 x 45 3150x560 355017
255 3 x 55 - 2 x 45 3150x560 355017
265 4 x 55 - 1 x 45 3150x560 355017
275 5 x 55 3150x560 355017
280 1 x 55 - 5 x 45 3700x560 355018
290 2 x 55 - 4 x 45 3700x560 355018
300 3 x 55 - 3 x 45 3700x560 355018
310 4 x 55 - 2 x 45 3700x560 355018
320 5 x 55 - 1 x 45 3700x560 355018
330 6 x 55 3700x560 355018
In line frame kit 355013
Header Low Loss DN80 Kit 355019
FRAME AND HEADER KIT SYSTEM DESIGN OPTIONS
2.1 FRAME AND HEADER KIT DESIGN OPTIONS
The Keston Heat boilers are suitable for use in a multiple boiler conguration. The multiple boiler system is available as a wall
or frame mounted side by side conguration with the use of the relevant frame / header kits. This gives opportunity to choose
the optimum footprint size or wall space for a given output. The table below states options available and gives the minimum
number of appliances required, the appropriate oor space & the kit product number (N.B. The kits do not include the boilers).
Side by side kits do not include the support frame as the boilers can be wall mounted but a frame kit is available if wall space
etc. does not facilitate boiler/header wall mounting.
Flue conguration for the appliance is C53 and C13 only (see appliance manual).
2 GENERAL DESCRIPTION OF CASCADE SYSTEMS